Find the faults

Level 10 of 33 in the Electrical lab: a free panel wiring exercise at Advanced level. A finished board with five faults hidden in it: a wrong neutral, a switch in the wrong conductor, a loose terminal, a wrong overload setting and a broken hold-in. Find them with dead tests first, fix them and test again.

AdvancedNot started

Goal

This board was wired by someone else and handed over as finished.

What you do

  1. Lock out the board at Q1, prove it dead, live-dead-live.
  2. Dead tests first: protective conductor continuity, insulation resistance, polarity (the Installation tester), then a visual check of every terminal against the schedule, and the torque screwdriver on every terminal.
  3. Fix what you find: remove or add the conductor, tighten the terminal, set the dial. One conductor per terminal.
  4. Restore power, run the live tests, try the circuits, and run the FAT.
  5. Hints: the lamp circuit has two faults; the motor control circuit has two; and one setting is wrong.

Done when

The factory acceptance test is marked against the panel you built.

  • 25 conductors in the wiring schedule
  • 5 dead checks before you touch the panel

Skills

Fault-finding at Advanced level.

Before you start

Level 9, Timers and relays, comes first. Do it first if the ideas are new to you.

Free, in your browser, nothing to install. Your work is saved on this device. Updated 1 Nov 2026.

33 levels

Levels in the Electrical lab

Lock out, wire, test and fault-find a control panel, then prove it with a factory acceptance test.

Wiring basics

Levels 1 to 10
  1. Start Meet the bench and your meter
  2. Start One lamp, one switch
  3. Start Two-way switching: a stair light
  4. Start A socket on an RCD
  5. Start Contactor with start and stop
  6. Start Direct-on-line motor starter
  7. Start Forward and reverse with an interlock
  8. Start Star-delta with a timer
  9. Start Timers and relays
  10. Start Find the faults

Electrical drawings

Levels 11 to 23
  1. Start Symbols you will meet
  2. Start How a drawing set is organised
  3. Start Read a power circuit
  4. Start Read a control circuit
  5. Start Read a PLC input and output drawing
  6. Start Terminal plans and cable lists
  7. Start Use the drawing to find a fault
  8. Start Draw your first circuit
  9. Start Draw a direct-on-line starter
  10. Start Draw a forward and reverse starter
  11. Start Draw the PLC input and output sheet
  12. Start Draw the panel layout and parts list
  13. Start Build what you drew

Control panels

Levels 24 to 33
  1. Start Commission the transfer-pump starter
  2. Start Fault-find the outfeed conveyor starter
  3. Start Commission the star-delta fan starter
  4. Start Commission the reversing conveyor starter
  5. Start Commission the overhead tank pump (Hand/Off/Auto)
  6. Start Commission the sorting station sensors
  7. Start Commission the variable-speed infeed conveyor drive
  8. Start Commission the 4-20 mA level loop
  9. Start Commission the pneumatic pusher station
  10. Start Commission the packing cell (capstone)

Part of the Electrical lab

Lock out, wire, test and fault-find a control panel, then prove it with a factory acceptance test.

Feeds these internships (training, not employment): Control Panel Design and Wiring, Commissioning and Maintenance, Instrumentation and Process Control.

About the Electrical lab

Ready for Find the faults?

Free, in your browser, with nothing to install.